Engineering Guide · CAN / CAN FD
Industrial CAN Bus Engineering: Isolation, CAN FD, Signal Integrity & Reliability
Updated October 17, 2026 · BITECH Engineering · Technical figures are taken from the cited standards and device datasheets; BITECH model data comes from the published product pages.
Quick answer: An industrial CAN network is reliable when its physical layer and system boundaries are right, not when its headline bit rate is high. Power and ground domains, common-mode range, cable topology, termination, EMC protection and controller/driver support decide whether frames arrive. Isolate CAN ports that cross ground domains or long, noisy cable runs. Keep standard Classical CAN controllers off CAN FD segments unless they are FD-tolerant. Consider CAN SIC transceivers when a fast CAN FD data phase must run on a non-ideal topology. Then validate the complete chain — transceiver, controller, Linux driver and bus-off recovery policy — on the real harness before deployment.
Industrial CAN Bus Architecture & Reliability Requirements
Start CAN hardware selection from the system boundary — which devices share power and ground, how far the cable runs and which frame formats must coexist — rather than from the protocol's maximum bit rate.
Why CAN Bus Still Matters in Industrial Automation
CAN remains common in machine controls, servo and motion networks, mobile robots, vehicle diagnostics and battery management systems. Its value comes from protocol mechanisms: non-destructive bitwise arbitration, CRC-based error detection, automatic retransmission and fault confinement that removes a persistently faulty node from the bus. Higher-layer protocols such as CANopen and SAE J1939 build on these mechanisms.
Arbitration guarantees that the highest-priority identifier wins access when the bus becomes idle. It does not by itself guarantee a fixed latency for every message. Worst-case response time depends on bus load, frame lengths, identifier assignment and error recovery, so it has to be calculated or measured for each network rather than quoted as a generic figure.
Common CAN Bus Failure Modes
Every CAN controller keeps a transmit error counter (TEC) and a receive error counter (REC). A node is error-active while both counters are below 128, becomes error-passive when either reaches 128 and goes bus-off when the TEC exceeds 255. A bus-off node stops transmitting until it is recovered. Most field faults show up as counter growth long before communication stops.
| Symptom | Likely physical cause | First check |
|---|---|---|
| Error frames that increase with bus load | Reflections from missing, extra or misplaced termination; long stubs | Power off, measure CAN_H–CAN_L resistance; scope the dominant-to-recessive edge |
| Errors only while VFDs, welders or contactors run | Ground potential difference, common-mode excursion, EMI coupling | Measure ground offset between nodes; review shield bonding; evaluate isolation |
| One node cycles error-passive → bus-off | Wrong bit timing, a Classical node on CAN FD traffic, local transceiver fault | ip -details -statistics link show can0; compare bit-timing settings |
| Works on the bench, fails in the field | Longer cable, different grounding, real noise sources | Repeat measurements on the installed harness |
| Errors only in the CAN FD data phase | Ringing, insufficient data-phase sample-point margin, transceiver loop delay | Lower the data bit rate, review sample point and delay compensation, consider CAN SIC |
Key Engineering Parameters Before Hardware Selection
| Parameter | Why it matters | What to record |
|---|---|---|
| Frame formats | Classical-only controllers cannot coexist with CAN FD traffic | Classical CAN, CAN FD, or both on the same segment |
| Nominal and data bit rate | Sets timing margin, cable length and transceiver requirements | Arbitration rate, data rate, sample points |
| Topology | Stubs and star points create reflections | Node count, trunk length, longest stub, star or linear |
| Power and ground domains | Decides whether isolation is needed | Supplies per node, cabinets, chassis or vehicle ground |
| Environment | Drives protection and component grade | Ambient range, ESD/EFT/surge levels, vibration |
| Software stack | Decides driver path and validation effort | OS, kernel/BSP, SocketCAN or vendor API, CANopen/J1939/proprietary |
Galvanic Isolation: When Isolated CAN Is Necessary
Isolate a CAN port when the nodes it connects do not share a solid, low-impedance ground reference — separate cabinets or supplies, long cable runs, drive-heavy floors or vehicle chassis segments. A short segment inside one cabinet with a verified common ground often runs reliably without isolation.
Ground Loops and Ground Potential Differences
A non-isolated transceiver references CAN_H and CAN_L to the local logic ground. When two nodes sit on grounds that differ by several volts — because of motor return currents, long earth paths or separate power supplies — that offset appears as common-mode voltage at the receiver. Standard transceivers tolerate only a limited common-mode range; the transceiver discussed in an EEVblog design review later in this guide is checked against a ±12 V receiver range, while an isolated part such as TI ISO1042 specifies ±30 V. Beyond the receiver's range, bits are misread; beyond the absolute maximum ratings, parts are damaged. Ground-return current flowing through the CAN reference conductor or shield also injects noise.
Isolated vs Non-Isolated CAN Architecture
| Deployment condition | Typical choice | Reason |
|---|---|---|
| Short segment inside one cabinet, one supply, verified common ground | Non-isolated is usually acceptable | Ground offset is small and controlled; lower cost and loop delay |
| Nodes in different cabinets or on different supplies | Isolated | Ground offset is unknown and can change with load |
| VFDs, servo drives, welders or large contactors nearby | Isolated, plus a defined shield and bonding strategy | Large return currents and fast transients in the ground system |
| Battery racks or BMS segments at different potentials | Isolated, preferably per channel | Segments may not share a ground plane |
| Vehicle or AGV with multiple chassis segments | Assess per architecture; isolation is common where CAN crosses segments | Depends on how the vehicle defines CAN ground |
Mixing isolated and non-isolated nodes on one bus is electrically valid. Isolation protects the node that has it; it does not make the other nodes immune, and it is not required on every node by default.
Isolated DC/DC Power and Signal Isolation
A digital isolator or isolated transceiver only creates an isolation domain if the bus-side transceiver is powered from a supply that is also isolated from logic ground. TI's ISO1042 documentation, for example, describes its protection as effective when the device is used together with isolated power supplies. If the bus-side supply is derived from the logic rail, or if CAN_GND, the shield or a protection component is tied back to logic ground, the barrier is bypassed. Review the isolated DC/DC converter's own isolation rating, any Y-capacitors across the barrier, and where CAN_GND and the shield terminate.
Understanding Isolation Ratings, CMTI and Bus Protection
A single "isolation voltage" figure is not enough to compare interfaces. Device datasheets separate several ratings, measured under different conditions:
| Rating | What it describes | ISO1042 example |
|---|---|---|
| Withstand isolation voltage (VISO) | Short-duration test across the barrier | 5000 VRMS for 1 minute (UL 1577) |
| Working isolation voltage (VIOWM) | Continuous voltage the barrier is rated to sustain | 1060 VRMS |
| Maximum transient isolation voltage (VIOTM) | Peak transient rating | 7071 VPK |
| CMTI | Common-mode transient slew rate tolerated without data errors | 100 kV/µs |
| Bus fault protection | DC voltage the CAN pins tolerate without damage | ±70 V |
| Receiver common-mode range | Common-mode voltage over which data is received | ±30 V |
| Maximum data rate | Isolation can limit the CAN FD data phase | Classical CAN to 1 Mbit/s, CAN FD to 5 Mbit/s |
Product-level figures such as "4000 V isolated" are normally withstand-type ratings. When comparing industrial PCs, ask which rating the figure refers to, the test standard and duration, the working voltage, and whether ESD/EFT/surge immunity was tested on the CAN port. BITECH's AE-3588BT page, for instance, states that its 4000 V figure is a withstand rating and that working-voltage data comes from the isolation test report. For the underlying principles, see Industrial PC Galvanic Isolation and Isolated vs Non-Isolated I/O.
Classical CAN vs CAN FD: Compatibility & Failure Modes
Classical CAN and CAN FD nodes can share a bus only if every Classical node is FD-tolerant, or if the CAN FD nodes transmit Classical frames only. A standard Classical CAN controller answers every CAN FD frame with an error frame.
Classical CAN vs CAN FD — Frame Structure and Data Rates
| Attribute | Classical CAN (CAN CC) | CAN FD | CAN XL |
|---|---|---|---|
| Data field | 0–8 bytes | 0–64 bytes (discrete length steps) | 1–2048 bytes (byte-wise) |
| Bit-rate phases | One bit rate for the whole frame | Arbitration at nominal rate; optional faster data phase (BRS) | Arbitration phase plus a faster XL data phase |
| Standard | ISO 11898-1 | ISO 11898-1 (since 2015 edition) | ISO 11898-1:2024 |
| Practical data-phase limit | Up to 1 Mbit/s for high-speed CAN | Set by transceiver and topology, e.g. 5 Mbit/s for ISO1042, 8 Mbit/s for SIC transceivers | Higher rates require CAN SIC XL transceivers |
The controller, the transceiver and the harness each impose a limit; the lowest one sets the usable data rate.
Why Legacy CAN Controllers May Fail on CAN FD Networks
A Classical controller expects a reserved bit where a CAN FD frame carries a recessive FDF bit. It treats that bit as a format violation and transmits an error frame, destroying the CAN FD frame on the bus. ISO 11898-1:2024 distinguishes nodes that support Classical frames only without tolerating CAN FD, nodes that tolerate CAN FD frames, and nodes that support CAN FD or CAN XL. A Classical-only node can communicate with CAN FD-capable nodes only while Classical frames are used.
Field example. In a March 2026 NXP Community thread, an engineer connected an S32K144 CAN FD channel and two Classical-only channels (one behind a TJA1051T transceiver) to the same bus. The first CAN FD transmissions produced 15 error frames; after that, CAN FD traffic passed and no further error frames appeared. NXP support explained that the Classical node sends active error flags until its error counters reach 128, after which it is error-passive or bus-off and stops disturbing the bus. The network appears to work only because the legacy node has silenced itself — it is no longer receiving reliably. NXP's recommended fix was a transceiver with CAN FD-passive support, such as specific variants of the UJA1169.
CAN FD Error Frames, Error Passive and Bus-Off
Diagnose mixed-network problems with error counters, not with "frames still arrive". Typical signs are a burst of error frames whenever CAN FD traffic starts, one node whose TEC/REC climbs quickly to the error-passive threshold, and repeated bus-off and restart events on that node. An error-passive node can still transmit but signals errors only passively, so it stops destroying frames while its own reception remains unreliable.
Mixed Network Design and Gateway Solutions
| Option | How it works | Trade-off |
|---|---|---|
| Upgrade the segment to CAN FD | Replace or update Classical-only nodes | Cleanest result; may not be possible for third-party devices |
| Classical frames only on the shared bus | CAN FD-capable nodes send Classical frames | Full compatibility; no CAN FD payload or rate benefit |
| FD-tolerant or FD-passive transceivers | Transceiver hides CAN FD frames from the legacy controller | Hardware change on legacy nodes; confirm the exact part variant |
| Separate channels | Legacy devices on one CAN port, CAN FD devices on another; the IPC bridges in software | Requires two independent controllers; adds bridging latency and ID mapping |
| Dedicated CAN/CAN FD gateway | External gateway translates between segments | Extra device and configuration; clear segment boundary |
Diagnostic sequence: list every node's controller capability → capture error frames and counters while CAN FD traffic starts → identify the node whose counters rise → confirm whether its controller and transceiver are FD-tolerant → choose one of the options above.
CAN SIC Transceivers & Signal Integrity
CAN SIC (Signal Improvement Capability) is a transceiver feature that actively suppresses ringing at the dominant-to-recessive edge and tightens bit-timing symmetry. It does not change the CAN FD protocol, the frame format or the controller.
What Is CAN SIC (Signal Improvement Capability)?
CAN SIC was first specified by CAN in Automation in CiA 601-4 and is now part of ISO 11898-2:2024, after which CiA withdrew CiA 601-4. CiA has also published a corrigendum proposal, CiA 140, to address inconsistencies in the published ISO 11898-2:2024 text. SIC transceivers are interoperable with conventional high-speed Classical CAN and CAN FD transceivers on the same bus, according to NXP's TJA1463 documentation.
Ringing, Reflections and High-Speed CAN FD
Every stub, star point and unterminated branch is an impedance discontinuity that reflects energy. Reflections are most harmful at the dominant-to-recessive transition, because the recessive state is not actively driven — only the termination pulls the bus back. At 5 Mbit/s a data-phase bit lasts 200 ns, so ringing that would be harmless in a 2 µs bit at 500 kbit/s can consume the sample-point margin.
Conventional CAN FD PHY vs CAN SIC PHY
| Attribute | Conventional CAN FD transceiver | CAN SIC transceiver (e.g. NXP TJA1463, TI TCAN1463-Q1) |
|---|---|---|
| Standard basis | ISO 11898-2:2016 | CiA 601-4, now ISO 11898-2:2024 |
| Ringing suppression | None; relies on termination and topology | Active suppression at the dominant-to-recessive edge |
| Datasheet data rate | Device-specific; e.g. isolated ISO1042 up to 5 Mbit/s | Classical CAN and CAN FD up to 8 Mbit/s |
| Topology tolerance | Best on linear buses with short stubs | NXP cites reliable 5 Mbit/s in larger topologies; TI cites multi-stub networks |
| Drop-in compatibility | — | Pin-compatible with common CAN FD transceivers per vendor (check variant) |
The 8 Mbit/s figure is a transceiver capability, not a guarantee for any harness. Usable data-phase rate still depends on the controller's timing, loop delay, node count, cable and stub lengths, which is why the full bus must be validated.
When to Consider CAN SIC for Industrial Networks
- Star or multi-stub topologies that cannot be rewired into a clean linear bus.
- Networks with many nodes that need a CAN FD data phase of 2 Mbit/s or more.
- Designs that may migrate toward CAN XL, where CiA lists CAN SIC XL transceivers with a FAST mode of up to 20 Mbit/s.
BITECH product pages do not list CAN SIC transceivers on current AX or AE models. Treat CAN SIC as an OEM/ODM evaluation item, not a standard feature.
CAN Bus Termination, Topology & Grounding
A linear high-speed CAN bus is terminated with one 120 Ω resistor at each physical end of the trunk — two in total, not one per node.
Why Two 120 Ω Terminators Are Required
The terminators match the characteristic impedance of the twisted pair, absorbing the wave at each end instead of reflecting it, and they discharge the bus into the recessive state after each dominant bit. Nodes in the middle of the trunk connect through short stubs and carry no termination.
Understanding the 60 Ω Resistance Measurement
With every node unpowered and no other parallel path, two 120 Ω terminators in parallel measure about 60 Ω between CAN_H and CAN_L. Each connected transceiver adds a high input resistance in parallel, so large networks read slightly lower.
| Reading | Most likely meaning |
|---|---|
| ≈ 60 Ω | Two terminators, correct for a linear bus |
| ≈ 120 Ω | One terminator missing or disconnected |
| ≈ 40 Ω | Three terminators — one extra, often an enabled termination inside a node |
| Very high / open | No termination or a broken conductor |
| Near 0 Ω | Short between CAN_H and CAN_L |
For the full field procedure, see CAN Bus 60 Ω Check.
Split Termination and Switchable Termination
Split termination replaces each 120 Ω resistor with two 60 Ω resistors whose centre point is connected to ground through a capacitor, filtering common-mode noise. Switchable termination lets one hardware design serve as an end node or a mid-bus node, but the switch becomes part of the termination network.
A December 2025 EEVblog design review of a TCAN1044A interface with MOSFET-switched split termination shows the typical traps. A reviewer noticed that placing the termination behind 10 Ω series resistors made it look like about 140 Ω to the bus instead of 120 Ω. Another pointed out that the MOSFET gates were referenced to board ground while the sources followed the bus, so common-mode excursions within the transceiver's ±12 V range could switch the termination unintentionally, and stressed that the network's behaviour when unpowered matters. The designer moved to an opto-isolated solid-state-relay approach based on a TI reference design. Before adopting switchable termination, verify the effective resistance including switch on-resistance, the common-mode behaviour and the state during power loss.
Stub Length, Cable Shielding and Grounding Strategy
Allowed stub length shrinks as the data-phase bit rate rises, because reflections must settle well within a shorter bit time. Use the limits in ISO 11898-2 guidance and the transceiver vendor's application notes for the actual bit rates, rather than one fixed length for all networks. Carry a CAN reference conductor (CAN_GND) with the pair when nodes are isolated or on different supplies. For shields, single-point bonding avoids low-frequency ground-loop currents, while bonding at both ends performs better at high frequencies when an equipotential bonding system exists. Decide per installation and document the choice.
Dual CAN Architecture for Industrial PCs, AMRs & BMS
Two CAN ports are only as independent as their controllers, transceivers and isolation domains. Check all three before relying on dual CAN to separate traffic.
Independent CAN Controllers and Isolation Domains
| Level | What it gives you | Question to ask the supplier |
|---|---|---|
| Independent controllers | Separate error counters; a bus-off on one channel does not stop the other | Are both ports native controllers, or is one behind a USB/SPI bridge? |
| Independent transceivers | A transceiver fault stays on one bus | Is each port driven by its own transceiver? |
| Independent isolation domains | No shared bus-side ground between the two networks | Does each channel have its own barrier and isolated supply, or do they share one? |
Dual CAN for AMR/AGV Motion and Diagnostics
A common AMR pattern places drive controllers on one channel and BMS, sensors, diagnostics and firmware download traffic on the other. Diagnostic bursts and large transfers then cannot consume motion-bus bandwidth, and a fault on the service bus does not take the drive bus off-line. See AMR Controller Solutions for platform options.
CAN Networks for Battery Energy Storage and BMS
Battery racks and energy-storage segments may sit at different potentials and do not always share a ground plane. Isolation per channel lets each CAN segment keep its own reference. BITECH's AE-3588BT, for example, lists two CAN 2.0B channels with 4000 V isolation, positioned for BMS aggregation in ESS gateways.
Vehicle CAN Gateways and Power Management
In vehicles, supply transients and CAN line protection are separate design questions. Ignition sensing, controlled shutdown, cranking dips and load dump belong to the power input; ISO 7637-2 tests address that path. The input range also has to match the vehicle bus: BITECH's AX-238BT page notes that a 9–36 V input cannot ride through the charging transients of a 48 V system without an external converter or a different input stage. Details are covered in Powering an Industrial PC in a Vehicle.
Functional Safety Boundaries
Dual CAN separates traffic; it does not create a safety function. Emergency stop and other safety functions need a safety chain designed and assessed to the applicable standard — for example IEC 61508 or ISO 13849 — with safety-rated components or protocols such as CANopen Safety (EN 50325-5). A general-purpose industrial PC with two CAN ports is not SIL- or PL-rated unless explicitly certified.
| Application | CAN A | CAN B | Isolation | Power notes |
|---|---|---|---|---|
| AMR / AGV | Drives (often CANopen CiA 402) | BMS, sensors, diagnostics | Recommended where drives and battery share long harnesses | Battery bus range, remote on/off |
| BESS / BMS gateway | Rack segment 1 | Rack segment 2 | Per channel | Site DC supply, power-loss behaviour |
| Vehicle gateway | Drivetrain bus | Body / telemetry bus | Depends on vehicle grounding | Ignition, cranking, load dump |
| Machine cell | Motion / I/O | Service and data logging | Cabinet-dependent | 24 V cabinet supply |
EMC Protection: ESD, EFT, Surge & Industrial Transients
Galvanic isolation and transient protection solve different problems. The barrier blocks ground-potential differences; TVS diodes, common-mode chokes, layout and shielding decide whether the port survives ESD, EFT and surge.
TVS Diodes and Common-Mode Chokes
Place TVS protection at the connector, with a short return path to the correct reference — the bus-side ground on an isolated port. Choose a working voltage above normal CAN levels and the expected fault voltage, and a clamping voltage below the transceiver's absolute maximum. TVS capacitance loads the bus and can unbalance CAN_H and CAN_L, so use low-capacitance, matched parts for CAN FD. Common-mode chokes reduce emissions and improve immunity, but some parts introduce ringing or asymmetry at high data rates; select chokes specified for CAN FD.
Isolation vs Surge Protection — Different Functions
An isolation rating describes the barrier. It is not the CAN port's surge immunity level, and neither is equivalent to a product certification. A product's EMC declaration applies to the tested configuration, ports and cabling, so a configuration change — an added isolated option, different cable, different grounding — may need re-verification.
IEC 61000-4-2 / -4-4 / -4-5 Testing
| Standard | Phenomenon | What a report should state |
|---|---|---|
| IEC 61000-4-2 | Electrostatic discharge | Contact/air levels, discharge points (connector, shield, enclosure), performance criterion |
| IEC 61000-4-4 | Electrical fast transient / burst | Level, coupling method (capacitive clamp for signal lines), criterion |
| IEC 61000-4-5 | Surge | Level, coupling network, line-to-ground or shield configuration, criterion |
Performance criteria are usually reported as A (normal operation within specification), B (temporary degradation with self-recovery) or C (loss of function requiring intervention). For a CAN port, request the criterion observed on the bus — for example, whether error frames or a bus-off occurred during the test.
| Port | Test | Level | Coupling / setup | Criterion | Report no. |
|---|---|---|---|---|---|
| CAN 1 | IEC 61000-4-2 | From report | Discharge points | A / B / C | From report |
| CAN 1 | IEC 61000-4-4 | From report | Capacitive clamp | A / B / C | From report |
| CAN 1 | IEC 61000-4-5 | From report | Coupling network | A / B / C | From report |
Automotive ISO 7637-2 Considerations
ISO 7637-2 covers electrical transients conducted along vehicle supply lines, so it applies to the industrial PC's power input, not to the CAN pair. Transients coupled onto other lines are addressed by ISO 7637-3, and CAN transceiver EMC is evaluated at component level under IEC 62228-3. Keep the supply-line and data-line evidence separate in test plans and reports.
Linux SocketCAN, CAN FD Drivers & Troubleshooting
A CAN port is ready for production on Linux when it appears as a native SocketCAN interface, accepts the required bit rate and data bit rate, reports error states correctly and recovers in a controlled way. Verify each point on the actual BSP image.
Native SocketCAN vs USB-CAN Vendor Drivers
SocketCAN exposes CAN controllers as network interfaces (can0, can1), configured with ip and tested with can-utils. Applications use standard sockets, so the same code runs on any SocketCAN driver. Adapters that depend on a vendor library work only where that library is supported and need separate validation. Several USB adapters have mainline SocketCAN drivers; the controller and driver behind each port should still be identified.
Checking CAN FD Support in Linux
CAN FD needs support at every layer: controller silicon, kernel driver, device tree or bus bridge configuration, and transceiver. Configuring fd on fails on a controller without CAN FD support, and the kernel requires the data bit rate to be at least the arbitration bit rate. After configuration, ip -details link show can0 shows the FD flag and both bit-timing sets.
# Show the current state, bit timing and error counters
ip -details -statistics link show can0
# Configure CAN FD (only if controller and driver support it)
sudo ip link set can0 down
sudo ip link set can0 type can bitrate 500000 dbitrate 2000000 fd on restart-ms 100
sudo ip link set can0 up
# Monitor traffic, then re-check state and counters
candump can0
ip -details -statistics link show can0
restart-ms 100 is a demonstration value. Choose automatic recovery according to the system's fault-handling strategy — see below.
Using candump, cansend, canbusload and canfdtest
| Tool | Purpose | Example |
|---|---|---|
| candump | Display, filter and log CAN traffic | candump -td can0 |
| candump (error frames) | Show error frames generated by the driver | candump can0,0:0,#FFFFFFFF |
| cansend | Send a single frame | cansend can0 123#DEADBEEF · CAN FD with BRS: cansend can0 123##1DEADBEEF |
| cangen | Generate test traffic | cangen can0 |
| canbusload | Calculate and display bus load | canbusload can0@500000 |
| canfdtest | Full-duplex test between a device under test and a host | DUT: canfdtest -v can0 · host: canfdtest -g -v can0 |
Diagnosing Bus-Off, Error Counters and Recovery
The -details -statistics output reports the controller state (ERROR-ACTIVE, ERROR-WARNING, ERROR-PASSIVE, BUS-OFF), the TX/RX error counters (berr-counter) and event counts for restarts, bus errors, lost arbitration, warnings, passive transitions and bus-off. With restart-ms 0 there is no automatic recovery, and a bus-off interface is restarted manually with ip link set can0 type can restart. Automatic restart restores communication after a transient fault, but on a permanently shorted or mis-configured bus it repeats error bursts. Applications that depend on the bus should supervise message timeouts rather than rely only on driver recovery.
What to Verify in an Industrial PC BSP
| Item | Pass condition |
|---|---|
| Kernel and driver | Kernel version, driver name and source (mainline or vendor) recorded |
| Interface type | Ports appear as native SocketCAN interfaces |
| CAN FD | fd on accepted at the target bit rate and data bit rate |
| Throughput | No RX overruns at the expected bus load (canbusload, cangen) |
| Fault handling | Short and open bus produce the expected states and recover as designed |
| Long-term stability | Error-free full-duplex run with canfdtest over the agreed duration |
CAN XL, CANsec & 10BASE-T1S: Future Industrial Networks
For most industrial projects today, CAN FD covers the bandwidth and ecosystem requirements. Evaluate CAN XL, CANsec or 10BASE-T1S when a requirement CAN FD cannot meet — larger payloads, data-link-layer security or Ethernet-native integration — and when silicon, software stacks and tools exist for the target platform.
CAN XL vs CAN FD
CAN XL is standardized in ISO 11898-1:2024 and extends the data field to 1–2048 bytes, adjustable in single-byte steps. Data-phase rates of 10 Mbit/s and above require CAN SIC XL transceivers. Nodes that implement CAN XL can transmit and receive all frame formats defined in ISO 11898-1:2024.
CANsec and Network Security
CANsec is a data-link-layer security protocol for CAN XL developed by CiA in CiA 613-2. A bit in the CAN XL control field marks secured frames, and a CANsec header carries cipher control information, a secure channel identifier and a freshness value. Key management is handled separately. Before planning on CANsec, confirm the current status of the specification and the availability of controllers and stacks that implement it.
CAN vs 10BASE-T1S for Robotics and Automation
10BASE-T1S is defined in IEEE 802.3cg-2019. It carries standard Ethernet frames at 10 Mbit/s, half-duplex, over a single twisted pair in a multidrop topology, and uses Physical Layer Collision Avoidance (PLCA) to schedule transmit opportunities. It is a short-reach PHY; onsemi documentation cites 25 m for multidrop segments.
| Attribute | CAN FD | CAN XL | 10BASE-T1S |
|---|---|---|---|
| Standard | ISO 11898-1 / -2 | ISO 11898-1:2024, ISO 11898-2:2024 | IEEE 802.3cg-2019 |
| Payload | Up to 64 bytes | 1–2048 bytes | Ethernet frame |
| Medium access | Bitwise arbitration | Bitwise arbitration | PLCA (round-robin transmit opportunities) |
| Software model | SocketCAN, CANopen, J1939 | CAN XL stacks, emerging | IP/Ethernet stack |
| BITECH status | Listed on selected models (see below) | Future technology — not yet validated on a BITECH SKU | |
When to Keep CAN and When to Evaluate Alternatives
- Keep CAN FD when the network carries short, prioritized control messages, the device ecosystem (drives, BMS, sensors) is CAN-based, and CANopen or J1939 tooling is already in place.
- Evaluate CAN XL when payloads exceed 64 bytes or when tunnelling higher-layer protocols over CAN is planned, and silicon is available for every node.
- Evaluate 10BASE-T1S when edge devices should join an IP/Ethernet architecture directly and segments are short.
Choosing a BITECH Industrial PC with CAN / CAN FD
Select a platform by verified interface facts — CAN type per channel, whether isolation is standard, optional or ODM and what its rating means, and the OS and driver path — rather than by the number of CAN connectors.
Native CAN vs Optional Isolated CAN
On several BITECH platforms isolation is a configuration choice. Specify it for drive networks, long or cross-domain cabling, vehicle power and high-EMI floors; omit it for clean cabinets with a unified ground to save cost and loop delay. Two CAN ports do not imply two isolated ports.
CAN 2.0B vs CAN FD Hardware Requirements
Confirm CAN FD per channel. A platform with CAN FD listed on one model and CAN 2.0A/B on another needs the exact configuration checked, and CAN FD in hardware does not by itself mean a native SocketCAN CAN FD driver on your image.
Linux, Windows and Driver Qualification
Ask for the driver path for each OS: native SocketCAN on Linux, and the vendor API or driver on Windows. Run the validation checklist above on the delivered BSP version.
OEM/ODM CAN Interface Customization
For volume projects, CAN channel count, isolation, connector type and BSP can be adjusted at board level. Send the requirement list in the RFQ checklist below.
| Model | Role | CAN (as published) | Isolation | Power / temperature | OS (as published) | Confirm before ordering |
|---|---|---|---|---|---|---|
| AX-130BT | Compact controller, AMR/AGV, motion | 2× CAN FD | Optional 4000 V rating | 9–36 V DC; −20 to +60 °C | Windows 11 Pro, Ubuntu | CAN FD driver on your image; isolation rating basis |
| AX-134BT | Multi-network field controller (4× GbE) | 2× CAN; spec table lists CAN 2.0A/B | Optional 4,000 V | 9–36 V DC; −20 to +60 °C | Windows 11 Pro, Ubuntu, Linux | CAN FD availability for your configuration |
| AX-238BT | 4-display HMI, vehicle cockpit | 2× CAN (2.0 mm header) | Non-isolated as standard; ODM 4000 V withstand | 9–36 V DC, 120 W; −20 to +60 °C, −40 to +80 °C option | Windows 10/11, Linux | CAN 2.0B or CAN FD per channel; driver |
| AE-3588BT | ARM edge AI, ESS/BMS gateway | 2× CAN 2.0B | Standard 4000 V (withstand) | 9–36 V DC; −40 to +80 °C | Android 12, Ubuntu 20.04, Debian 11 | Working voltage from isolation test report; CAN FD not listed |
Discuss Your CAN Interface Requirements
Send the frame formats, bit rates, port count, grounding topology and OS. A BITECH engineer will map them to a configuration and state which items are standard, optional or ODM.
Discuss Your CAN Interface RequirementsIndustrial CAN Bus Engineering FAQ & RFQ Checklist
Does an industrial CAN bus always require galvanic isolation?
No. Isolation is needed when nodes do not share a reliable ground reference — separate cabinets or supplies, long runs, drives and welders, battery racks or vehicle chassis segments. A short CAN segment inside one cabinet with a verified common ground often works without isolation, at lower cost and loop delay.
Can Classical CAN and CAN FD nodes share the same network?
Only under conditions. A standard Classical CAN controller sends error frames when it sees a CAN FD frame, so the shared bus must either carry Classical frames only, or every Classical node must be FD-tolerant, for example through an FD-passive transceiver. Otherwise, split the nodes across separate channels or use a gateway.
What is the difference between CAN FD and CAN SIC?
CAN FD is a protocol; CAN SIC is a transceiver feature. CAN FD defines larger payloads and a faster data phase. CAN SIC transceivers, now specified in ISO 11898-2:2024, actively suppress ringing so a CAN FD data phase can run faster on non-ideal topologies. SIC transceivers such as TJA1463 and TCAN1463-Q1 are specified up to 8 Mbit/s.
Why does a terminated CAN bus measure about 60 Ω?
Because two 120 Ω terminators in parallel equal 60 Ω. With all nodes unpowered, a reading near 60 Ω between CAN_H and CAN_L indicates both ends are terminated; about 120 Ω means one is missing and about 40 Ω means an extra terminator is enabled.
Does an isolated CAN port also require isolated power?
Yes. The bus-side transceiver must be powered from a supply that is isolated from logic ground, typically an isolated DC/DC converter. If the bus side is powered from the logic rail, or CAN_GND is tied to logic ground, the isolation barrier is bypassed.
How do I verify SocketCAN and CAN FD support in Linux?
Configure the port with ip link set can0 type can bitrate … dbitrate … fd on and check the result with ip -details link show can0. The command fails if the controller or driver lacks CAN FD support. Then test traffic with candump and cansend, measure load with canbusload and run canfdtest for stability.
Can dual CAN channels be used for motion control and diagnostics?
Yes, if the channels have independent controllers. Placing drives on one channel and BMS, diagnostics and firmware traffic on the other keeps service traffic off the motion bus and limits a bus-off to one network. Dual CAN does not make the system functionally safe; safety functions need a separately assessed safety chain.
What information is required for a custom CAN industrial PC?
The application and environment, frame formats and higher-layer protocol, number of ports, isolation requirement and its basis, bit rates and topology, OS and driver needs, supply and EMC requirements, and expected quantity. The checklist below lists every item.
RFQ Checklist for CAN Interface Projects
- Application and target environment (cabinet, vehicle, outdoor, ESS site)
- Classical CAN, CAN FD, CANopen, J1939 or proprietary protocol
- Number of CAN ports; independent controllers required?
- Isolation requirement and its basis (working voltage, withstand test, separate grounds)
- Bit rate and data bit rate, maximum bus length, topology and node count
- Linux or Windows; kernel, driver and API requirements
- Supply voltage, ignition input, EMC levels and temperature range
- Expected quantity, project phase and validation evidence needed